08 System Commissioning
55
User Manual V1.2-2025-04-15
Parameter Description
Start-up Grid
Connection Frequency
Upper Limit
The inverter cannot connect to the grid if it is powered on for the rst
connection and the grid frequency is higher than the Start-up Grid
Connection Frequency Upper Limit.
Start-up Grid
Connection Frequency
Lower Limit
The inverter cannot connect to the grid if it is powered on for the rst
connection and the grid frequency is lower than the Start-up Grid
Connection Frequency Lower Limit.
Start-up Grid
Connection Waiting
Time
The waiting time for connecting the inverter to the grid when the
inverter is powered on for the rst connection.
Start-up Grid
Connection Power
Loading Rate (0.1%Pn/
min)
Set the percentage of incremental output power per minute when
the inverter is powered on for the rst connection.
Reconnection Voltage
Upper Limit
In some countries/regions, when the inverter is shut down due to a
fault protection, it is not allowed to reconnect to the grid if the grid
voltage is higher than the set value of the Reconnection Voltage
Upper Limit.
Reconnection Voltage
Lower Limit
In some countries/regions, when the inverter is shut down due to a
fault protection, it is not allowed to reconnect to the grid if the grid
voltage is lower than the set value of the Reconnection Voltage
Lower Limit.
Reconnection
Frequency Upper Limit
In some countries/regions, when the inverter is shut down due to
a fault protection, it is not allowed to reconnect to the grid if the
grid frequency is higher than the set value of the Reconnection
Frequency Upper Limit.
Reconnection
Frequency Lower Limit
In some countries/regions, when the inverter is shut down due to a
fault protection, it is not allowed to reconnect to the grid if the grid
frequency is lower than the set value of the Reconnection Frequency
Lower Limit.
Reconnection Waiting
Time
Set the waiting time for the inverter to restart after a grid failure is
restored.
Reconnection Power
Loading Rate (0.1%Pn/
min)
Set the percentage of incremental output power per minute when
the inverter is not powered on for the rst connection.
For example, setting Reconnection Power Loading Rate to 10 means
the reconnection slope is 10%Prated/min.
LVRT Enable
Low voltage ride-through (LVRT) refers to the situation, when the grid
experiences a short-term low voltage abnormality, the inverter cannot
immediately disconnect from the grid and has to work for a period of
time. Enable this function, the inverter's LVRT is being activated.
LVRT Depth n
The ratio of the ride through voltage to the rated voltage at a feature
point during LVRT, n= 1, 2, 3, 4, 5, 6, 7.
Hold Time n
The ride through time at a feature point during LVRT, n= 1, 2, 3, 4, 5,
6, 7.
Judgment Threshold of
Entering LVRT
Set the threshold for triggering LVRT. The threshold settings should
meet the local grid standard.
Judgment Threshold of
Exiting LVRT
Set the threshold for exiting LVRT. The threshold settings should meet
the local grid standard.