J. STARTUP AND OPERATION
J.3 Dip Switches
Auxiliary dip switch controls are located behind front
panel,through an opening below the control panel.
To access, remove front panel.
Dip switches are accessible without opening the
control box. Unit must be powered OFF to
effectively change their status.
Factory settings for dip switches will be in the
DOWN position.See Table 5-Dip Switch Functions
for functions of each dipswitch position.
Dip Switches
Figure J.3.1 (Dipswitch Location on Unit)
Figure J.3.2 (Dip Switches)
UP
Dow
n
Dip switch
Freeze guard
Setpoint Limit 2
Setpoint Limit 1
Wall Thermostat enable
Electric heat only (for Heat Pumps )
Table J.3.3 (DIP SWITCH FUNCTIONS)
No. UP DOWN REMARKS DEFAULT
1 DOWN
2 DOWN
6
*
5
UP*UP
68---75°F
UP*DOWN
63---80°F
DOWN*UP
65---78°F
DOWN*DOWN
61---86°F
(full range)
Two configurations (5* 6)
combine to selec t set point
range.
When set point limit set, dis-
play al
wa
ys sh
o
ws full
range.
DOWN*DOWN
61---86°F
7 Freeze Guard Disable Freeze Guard Enable DOWN
Electric Heat Only
Wall Thermostat Enable
Heat Pump
Control Panel Enable
For Heat Pump unit only.
Electric Heating Only/Emergency Heat (For Heat Pump Units Only)
This setting is typically used for Emergency Heating.
Wall Thermostat Enable
A wired wall thermostat can be connected to the unit. If it is, this dipswitch must be moved to the Wall
Thermostat Enable Position, before the wall thermostat will begin control.
Setpoint Temperature Limits
Provides a restricted range of temperature control.
Room Freeze Protection
If unit senses a room temperature below 40°F, the fan motor and electric strip heat will turn on and
warm the room to 50°F. The fan stops a short time after the temperature is satisfied.