2.3 CONDENSATE DISCHARGE CONNECTION
Because of the heat recovery system (the exhaust air is cooled by the air supplied into the heat exchanger), the
humidity contained in the internal air condenses inside the unit.
For correct operation of the heat recovery unit, it is necessary to connect one condensation discharge to the home
hydraulic system (discharge). Also, in order for the condensation water to correctly flow out and avoid air from
being sucked in, the condensation discharge must always feature a special trap installed by the installer;
There are 3 condensation discharges on the machine:
2 are for ceiling-mounting, 1 is for wall-mounting;
Only 1 of the 3 discharges will be used, based on ceiling or wall mounting and based on where the air exhaust is
positioned;
For installation of the condensation discharge, follow these rules:
• set up a slope of at least 2% to the discharge pipe;
• allow the possibility of disconnecting the discharge pipe for any maintenance (especially with ceiling
installation);
• make sure that the discharge end of the pipe is at least below the level of the trap water;
• make sure that the trap is always full of water and at a sufficient height (at least 40-50mm)
Install the condensation discharge trap on the exhaust side of the unit to avoid unpleasant odours in the room air
Condensation Discharge horizontal installation Condensation discharge Vertical installation
CONDENSATION
DISCHARGE
CONDENSATION
DISCHARGE
ELECTRICAL CABLE
INPUT