49 Automatic settings
Control System KNX WS1000 Style • Version: 28.05.2018 • Technical changes and errors excepted.
Press the button to set the indoor temperature above which the ventilation will be
switched on at night. Until an indoor sensor is selected, the indoor temperature will be
disregarded.
Setting the temperature:
Adjust the value for the desired room temperature using the
arrow buttons. Pre-setting: 21.0 °C.
Shutting off ventilation:
If ventilation is to be independent of indoor temperature, press
the button labelled OFF.
Confirm your setting with the OK button.
Press the button to set the air humidity above which the ventilation will be switched on
at night. Until an indoor sensor is selected, the air humidity will be disregarded.
Setting humidity:
Adjust the value for the desired humidity using the arrow buttons.
Pre-setting: 80%.
Shutting off ventilation
: If ventilation is to be independent of air humidity, press the
button labelled OFF.
Confirm your setting with the OK button.
Press the button to set the CO
2
content of the room air to be ventilated. As long as no
CO
2
sensor is selected, the CO
2
content is not taken into account.
Setting CO
2
: Use the upper arrow keys to set the value from which the ventilation starts
at the lowest preset speed. Default: 700 ppm.
Use the lower arrow keys to set the value at which ventilation takes place at the highest
specified speed. Default: 1500 ppm.
The speed is automatically adjusted between the two values.
Shutting off ventilation:
If ventilation is to be independent of the CO
2
content, press the
Off button.
Confirm your setting with the OK button.
Press the button to set the supply air temperature block (summer operation). With WL-
Z supply air units, the supply air temperature is recorded by a thermometer integrated
into the WL-Z. With devices from other manufacturers the outdoor temperature at the
weather station is used as the supply air temperature.
Indoor Temp
For all ventilation units.
Temp. Ventilation
Air Humidity
For all ventilation units.
Humidity Ventil.
CO2
For all ventilation units but only if a CO
2
sensor is
installed.
Supply-Air Temp.
Only for WL-Z
and ventilation units at MF output/RF Relay.