50 Automatic settings
Control System KNX WS1000 Style • Version: 28.05.2018 • Technical changes and errors excepted.
Enable: If the supply air unit should be closed when the supply air temperature is
warmer than the room temperature, select Yes.
Disable:
If the supply air unit should also then be/remain open when the supply air tem-
perature is warmer than the room temperature, select No (default setting).
Confirm your setting with the OK button.
Press the button to set the ventilation levels of the motorised roof ventilators. The fur-
ther the indoor temperature and air humidity lie above the reference values, the higher
the ventilator shifts.
Use the arrow buttons to change the start and maximum values according to your
wishes. Default setting: Start with level 1, maximum level 8 (full level utilisation).
Confirm your setting with the OK button.
Press the button to set the minimum and maximum ventilation speed of the motorised
roof ventilators. The further the indoor temperature and air humidity lie above the ref-
erence values, the higher the ventilator shifts.
Use the arrow buttons to change the start and maximum values according to your
wishes. Default setting: Start with 0%, maximum 100% (full level utilisation).
Confirm your setting with the OK button.
Press the button to set the times for night-time re-cooling. The button is only activated
once the general settings for night-time re-cooling have been configured.
System > Automatic Settings > General Settings > Night-time Cooling
3.3. Set night-time re-cooling (ventilation)
Press Select to select the time during which the night-time re-cooling will operate. Ac-
tivate one or more periods on the list.
Confirm your setting with the OK button.
To change any of the time periods, press Timer.
3.3. Set timer
Be careful that your settings for timed closure do not prevent night-time re-cooling op-
erations! A set supply air temperature block can also prevent night-time re-cooling.
Exhaus Air Levels
Only for air supply on RF-VM.
Ventilation Levels
Min. Exhaust Level
Only for WL400/800.
Max. Exhaust Level
Night-time Cooling
Not on fresh air/heating-combos on RF-VM.