Elsner KNX WS1000 Style handleiding

140 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 39 van 140
37 Automatic settings
Control System KNX WS1000 Style • Version: 28.05.2018 • Technical changes and errors excepted.
ture falls below the set value, select No. When the rain or wind alarm is triggered, the
shade will be retracted nonetheless (the alarm has priority over blocking temperature).
Confirm your setting with the OK button.
Press the button to active or deactivate the frost alarm for this shade. The frost alarm
retracts the sun shade if the outdoor temperature is low and it is raining/snowing at the
same time. This protects external shades from icing and from damage through move-
ment when the rails are iced up.
The conditions for the triggering of the frost alarm (outdoor temperature, period) are
defined in the menu „General Settings“.
System > Automatic Settings > General Settings > Frost Alarm
3.3. Adjust frost alarm
No time opening takes place in case of frost alarm.
When the frost alarm is triggered, manual operation of the shade is initially blocked.
You can remove the block manually however. To do this select the appropriate shade
in the Manual menu and press the frost alarm button. If the button is shown normally
(black writing), the block has been removed. The block will then be first active for this
drive again if it is reactivated maually or the next time the frost alarm is triggered.
Please note that the shade rails or other mechanical components can remain iced even
when the outdoor temperature has already risen to a relatively high value.
ATTENTION
Damage to property by moving frozen shades!
The drive and curtain can be damaged if a frozen outdoor shading
system is used.
•For sensitive curtains, set the frost alarm range generously.
•Before manually switching off the frost alarm, make sure that the
rails are not iced up.
Activate:
If the sun shade is to be retracted when there is a frost alarm, select Yes.
Deactivate:
If the sun shade should offer shade regardless of the frost risk, select No
(default setting).
Confirm your setting with the OK button.
Press the button to set the wind alarm. The wind alarm protects the system from dam-
age by retracting the blind respectively the roller shutter.
Adjust values:
Use the arrow keys to adjust the value for wind speed and the length of
time by which it must have been exceeded.
Frost Alarm
Wind Alarm

Bekijk gratis de handleiding van Elsner KNX WS1000 Style, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkElsner
ModelKNX WS1000 Style
CategorieNiet gecategoriseerd
TaalNederlands
Grootte12479 MB