33 Transfer protocol
Room Controller Cala Touch KNX • Version: 13.07.2022 • Technical changes and errors excepted.
5. Transfer protocol
Units:
Temperatures in degrees Celsius
Air humidity in %
Absolute air humidity in g/kg and/or g/m
3
CO
2
content in ppm
Variables in %
5.1. List of all communications objects
Abbreviation flags:
C Communication
R Read
WWrite
T Transfer
UUpdate
No. Text Function Flags DPT type Size
Display and user interfaces (objects 1-124)
for all models
1 Software version Output R-CT [217,001]
DPT_Version
2 bytes
21 Date / time Input -WCT [19.001] DPT_-
DateTime
8 bytes
22 Date Input -WCT [11.1] DPT_Date 3 bytes
23 Time Input -WCT [10.1] DPT_-
TimeOfDay
3 bytes
25 Screen brightness in % Input RWC- [5.1] DPT_Scaling 1 byte
26 Screen save (1=ON | 0=OFF) Input RWC- [1.1] DPT_Switch 1 bit
27 Screen saver illumination (1=ON |
0=OFF)
Input RWC- [1.1] DPT_Switch 1 bit
28 Screen saver wait time in seconds Input RWC- [7.005] DPT_-
TimePeriodSec
2 bytes
29 Screen no touch wait time in
seconds
Input RWC- [7.005] DPT_-
TimePeriodSec
2 bytes
30 Display language Input RWC- [234.001]
DPT_LanguageC-
odeAlpha2_ASCII
2 bytes
31 Button tone (1=ON | 0=OFF) Input RWC- [1.1] DPT_Switch 1 bit
34 Switch Light 1 on/off Input/
Output
RWCT [1.1] DPT_Switch 1 bit
35 Dim Light 1 Output R-CT [3.7] DPT_Con-
trol_Dimming
4 bit