20 Part Number: 9291458 11/17
Installation Section 2
FORCEDAIR REFRIGERATED DROPIN UNITS
N8100-FA
11.00”
(28cm)
Counter Cutout Dimensions
22.0” (56cm)
Air duct dimensions
to match condenser face
Are Model Specic
1. Install partitions between self-contained refrigerated
drop-in units and other electrical appliances if they
are located in the same cabinet. Partitions must fully
extend front to back and top to bottom.
2. Install a GFCI receptacle a minimum of 14” (36cm) up
from the cabinet bottom inside the partitions. Run the
outlet to a switch. With limited access to the control, a
switch will make it easy to turn the unit off for defrost.
3. The unit requires airflow to the compressor. One louver
is provided with each unit.
NOTE: Any restriction to the proper air flow will void the
compressor warranty.
• A 13” x 25” (33 cm x 64 cm) louver is provided by
Delfield and must be installed in the counter in front
of the condenser. The louver cutout dimension is 22”
x 11” (56 cm x 28 cm).
• The rear must have an opening for removal of
heated air. The opening must be at least 174in
2
(1123cm
2
).
Discharge Air
Fresh Air
Cutout
Louver
Condenser
4. Place the condensing unit through the counter cutout.
5. A gasket is installed in the flange of each unit.
The weight of the unit on the gasket forms a seal
preventing liquids from seeping into the cut-out
opening.