INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Appendix: Technical data
Specication Abbr. Unit HCV 460 P2
Max. ow at 100Pa V
100Pa
m/h 460
Max. rated ow at 100Pa V
max nom.
m/h 360
Operating range DIBt V
DIBt
m/h
70 - 360
Working range Passivhaus at 100Pa V
PHI
m/h 106 - 270
EN 13141-7 reference ow @50Pa V
REF
m/h 252
Performance
Temperature eciency in accordance
with EN13141-7l
h
SUP
% 86
Filters in accordance with EN779: 2012 class - G4/G4 (F7 optional)
Filters in accordance with ISO 16890
class -
ISO Coarse (epM1 > 50%
optional)
Ambient temperature for installation t
SURR
°C from +12 to +40
Outdoor temperature range without
installed preheater
t
ODA
°C from -12 to +50
Outdoor temperature with pre-heater
installed
t
ODA
°C from -25 to +50
Maximum absolute humidity
of extract air
x g/kg 10
Cabinet:
Dimensions (without brackets) W x H x D mm 540 x 1050x549 **
Spigots/duct connections Ø mm Ø160 - female
Weight m kg 40
Thermal conductivity -
polystyrene insulation
l
W/(mK) 0.031
Heat transfer coecient -
polystyrene insulation
U
W/(m
2
K)
U<1
Fire class - polystyrene insulation - -
DIN 4102 Class B2
EN 13501 Class E
Leakage (outside and inside) in
accordance with EN 13141-7
< 2 % (Class A1)
Drainage hose Ø/length " / m 3/4” - 2 m
Cabinet colour RAL - 9016
Electrical
Voltage U
V
230
Max. power consumption
(without/with preheater)
P
W
230/2080
Frequency f Hz 50
IP class class - 21
* The use of the preheating coil is recommended at outdoor temperatures below -3°C to
ensure balanced operation
** +20mm tting