Handleiding
Je bekijkt pagina 13 van 72

5 Preparation
Installer and user reference guide
13
RXYTQ8~16T7YF
VRV IV system air conditioner
4P388989-1A – 2015.07
Size up
HP class Piping outer diameter size (mm)
Gas pipe Liquid pipe
8 19.1 → 22.2 9.5 → 12.7
10 22.2 → 25.4
(a)
12+14 28.6
(b)
12.7 → 15.9
16 28.6 → 31.8
(a)
18~22 15.9 → 19.1
24 34.9
(b)
26~34 34.9 → 38.1
(a)
19.1 → 22.2
36~48 41.3
(b)
(a) If size is NOT available, increase is NOT allowed.
(b) Increase is NOT allowed.
▪ The pipe thickness of the refrigerant piping shall comply with the
applicable legislation. The minimal pipe thickness for R410A
piping must be in accordance with the table below.
Pipe Ø (mm) Minimal thickness t (mm)
6.4/9.5/12.7 0.80
15.9 0.99
19.1/22.2 0.80
28.6 0.99
34.9 1.21
41.3 1.43
▪ In case the required pipe sizes (inch sizes) are not available, it is
also allowed to use other diameters (mm sizes), taken the
following into account:
▪ Select the pipe size nearest to the required size.
▪ Use the suitable adapters for the change-over from inch tomm
pipes (field supply).
▪ The additional refrigerant calculation has to be adjusted as
mentioned in "6.7.3 To determine the additional refrigerant
amount"on page23.
5.3.3 To select refrigerant branch kits
Refrigerant refnets
For piping example, refer to "5.3.2 To select the piping size" on
page12.
▪ When using refnet joints at the first branch counted from the
outdoor unit side, choose from the following table in accordance
with the capacity of the outdoor unit (example: refnet joint a).
Outdoor unit capacity type
(HP)
2 pipes
8~10 KHRQ22M29T9
12~22 KHRQ22M64T
24~48 KHRQ22M75T
▪ For refnet joints other than the first branch (example refnet joint b),
select the proper branch kit model based on the total capacity
index of all indoor units connected after the refrigerant branch.
Indoor unit capacity index 2 pipes
<200 KHRQ22M20T
200≤x<290 KHRQ22M29T9
290≤x<640 KHRQ22M64T
≥640 KHRQ22M75T
▪ Concerning refnet headers, choose from the following table in
accordance with the total capacity of all the indoor units connected
below the refnet header.
Indoor unit capacity index 2 pipes
<200 KHRQ22M29H
200≤x<290
290≤x<640 KHRQ22M64H
(a)
≥640 KHRQ22M75H
(a) If the pipe size above the refnet header is Ø34.9 or more,
KHRQ22M75H is required.
INFORMATION
Maximum 8 branches can be connected to a header.
▪ How to choose an outdoor multi connection piping kit. Choose
from the following table in accordance with the number of outdoor
units.
Number of outdoor units Branch kit name
2 BHFQ22P1007
3 BHFQ22P1517
INFORMATION
Reducers or T-joints are field supplied.
NOTICE
Refrigerant branch kits can only be used with R410A.
5.3.4 About the piping length
Make sure to perform the piping installation within the range of the
maximum allowable pipe length, allowable level difference and
allowable length after branching as indicated below.
Definitions
Term Definition
Actual piping length Pipe length between outdoor
(a)
and indoor
units.
Equivalent piping
length
(b)
Pipe length between outdoor
(a)
and indoor
units.
Total piping length Total piping length from the outdoor
(a)
to all
indoor units.
H1 Difference in height between outdoor and
indoor units.
H2 Difference in height between indoor and
indoor units.
H3 Difference in height between outdoor and
outdoor units.
(a) If the system capacity is >16HP, re-read "the first outdoor
branch as seen from the indoor unit".
(b) Assume equivalent piping length of refnet joint=0.5m and
refnet header=1m (for calculation purposes of equivalent
piping length, not for refrigerant charge calculations).
5.3.5 Piping length: VRV DX only
For system only containing VRVDX indoor units:
System setup
Example Description
Example 1.1
a
A
h i j k l m n
B C D E F G
p
b c d e f
1 2 3 4 5 6 7
8
g
H1
H2
Single outdoor
Branch with refnet joint