5 Preparation
Installer and user reference guide
12
RXYTQ8~16T7YF
VRV IV system air conditioner
4P388989-1A – 2015.07
4 Calculate the refrigerant density taking the volume of the room
where the indoor unit is installed and the adjacent room. Install
ventilation openings in the door of adjacent rooms until the
refrigerant density is smaller than the maximum concentration
level.
5.3 Preparing refrigerant piping
5.3.1 Refrigerant piping requirements
NOTICE
The refrigerant R410A requires strict cautions for keeping
the system clean, dry and tight.
Clean and dry: foreign materials (including mineral oils
or moisture) should be prevented from getting mixed
into the system.
Tight: R410A does not contain any chlorine, does not
destroy the ozone layer, and does not reduce earth's
protection against harmful ultraviolet radiation. R410A
can contribute slightly to the greenhouse effect if it is
released. Therefore we should take special attention to
check the tightness of the installation.
NOTICE
The piping and other pressure-containing parts shall be
suitable for refrigerant. Use phosphoric acid deoxidised
seamless copper for refrigerant.
Foreign materials inside pipes (including oils for fabrication) must
be ≤30 mg/10 m.
Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.
Pipe Ø (mm) Temper grade of piping material
≤15.9 O (annealed)
≥19.1 1/2H (half hard)
All piping lengths and distances have been taken into
consideration (see "5.3.4About the piping length"on page13).
5.3.2 To select the piping size
Determine the proper size referring to following tables and reference
figure (only for indication).
A
B B B
C
D
E
x
y
b
a
1 2 3 4
b
1,2,3,4 VRVDX indoor unit
a,b Indoor branch kit
x,y Outdoor multi connection kit
A, B, C: Piping between outdoor unit and (first)
refrigerant branch kit
Choose from the following table in accordance with the outdoor unit
total capacity type, connected downstream.
Outdoor unit
capacity type (HP)
Piping outer diameter size (mm)
Gas pipe Liquid pipe
8 19.1 9.5
10 22.2 9.5
12~16 28.6 12.7
18~22 28.6 15.9
24 34.9 15.9
26~34 34.9 19.1
36~48 41.3 19.1
D: Piping between refrigerant branch kits
Choose from the following table in accordance with the indoor unit
total capacity type, connected downstream. Do not let the
connection piping exceed the refrigerant piping size chosen by the
general system model name.
Indoor unit capacity
index
Piping outer diameter size (mm)
Gas pipe Liquid pipe
<150 15.9 9.5
150≤x<200 19.1
200≤x<290 22.2
290≤x<420 28.6 12.7
420≤x<640 15.9
640≤x<920 34.9 19.1
≥920 41.3
Example:
Downstream capacity for E=capacity index of unit 1
Downstream capacity for D=capacity index of unit 1+capacity
index of unit 2
E: Piping between refrigerant branch kit and
indoor unit
Pipe size for direct connection to indoor unit must be the same as
the connection size of the indoor unit (in case indoor unit is VRVDX
indoor).
Indoor unit capacity
index
Piping outer diameter size (mm)
Gas pipe Liquid pipe
15~50 12.7 6.4
63~125 15.9 9.5
200 19.1
250 22.2
When the equivalent pipe length between outdoor and indoor
units is 90 m or more, the size of the main pipes (both gas side
and liquid side) must be increased. Depending on the length of the
piping, the capacity may drop, but even in such a case the size of
the main pipes has to be increased. More specifications can be
found in the technical engineering data book.
a
e
b c
d
a Outdoor unit
b Main pipes
c Increase if the equivalent piping length is ≥90m
d First refrigerant branch kit
e Indoor unit