6 | Installation
Installer reference guide
43
ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B +
RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B +
ARXF50~71A2V1B
R32 split series
4P513661-7H – 2019.12
Wire type Installation method
Single-core wire
c b
c
aa
A
AA´
A´
a Curled single-core wire
b Screw
c Flat washer
Stranded conductor wire
with round crimp-style
terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
O Allowed
X NOT allowed
Tightening torques
Item Tightening torque (N•m)
M4 (X1M) 1.2~1.3
M4 (earth)
▪ The earth wire between the wire retainer and the terminal must be longer than
the other wires.
1-3
6.7.4 Specifications of standard wiring components
Component
Power supply cable Voltage 220~240V
Phase 1~
Frequency 50Hz
Wire sizes 3-core cable
2.5mm2~4.0mm
2
H05RN-F (60245 IEC 57)
Interconnection cable
(indoor↔outdoor)
4-core cable
1.5mm
2
~2.5mm
2
and applicable for
220~240V
H05RN-F (60245 IEC 57)