Daikin RXM25N2V1B9 handleiding
Handleiding
Je bekijkt pagina 44 van 68

6 | Installation
Installer reference guide
44
ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B +
RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B +
ARXF50~71A2V1B
R32 split series
4P513661-7H – 2019.12
Component
Recommended circuit breaker RXM71N
RXP50~71M
RXF50+60B
RXF71A
ARXF50~71A
20A
(a)
ARXM60+71N
RXM60N
16A
ARXM50N
RXM42+50N
RXA42+50B
RXJ50N
13A
Earth leakage circuit breaker MUST comply with applicable legislation
(a)
Electrical equipment complying with EN/IEC 61000-3-12 (European/International
Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current >16A and
≤75A per phase).
6.7.5 To connect the electrical wiring on the outdoor unit
1 Remove the switch box cover.
2×
2
1
1
2 Strip insulation (20mm) from the wires.
a b
a Strip wire end to this point
b An excessive strip length may cause electrical shock or leakage
3 Open the wire clamp.
4 Connect the interconnection cable and power supply as follows:
50 Hz
220-240 V
c d
f
a b e
a Interconnection cable
b Power supply cable
c Circuit breaker
d Earth leakage circuit breaker
e Power supply
Bekijk gratis de handleiding van Daikin RXM25N2V1B9, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Daikin |
Model | RXM25N2V1B9 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 8936 MB |