16 | Unit installation
Installer and user reference guide
53
FXNA-A
VRV system air conditioner
4P785124-1 – 2024.09
Fixing the unit. Level the unit with the levelling screws (accessory). If the floor is
too uneven to level the unit, place the unit on a flat and levelled base. If the unit
is in danger of falling over, fasten it to the wall using factory-made holes or to the
floor using floor fasteners (field supply).
NOTICE
Do NOT install the unit tilted. Possible consequence: If the unit is tilted against the
direction of the condensate flow (the drain piping side is raised), the float switch
might malfunction and cause water to drip.
Wall-mounted installation
c
A
B
a
a
760
b≥100
A Maintenance area width
B Air inlet grille width
a Air outlet direction
b Air inlet grille height
c Air inlet direction
Class A(mm) B(mm)
20, 25, 32 1350 660
40, 50 1550 860
63 1750 1060