12 Unit installation
Installation and operation manual
16
FXFA20~125A2VEB
VRV system air conditioner
3P599604-1E – 2022.02
≥1500 ≥500 ≥200
a
A A A
b c
a Air outlet and corners open
b Air outlet closed, corners open (optional blocking pad kit
required)
c Air outlet and corners closed (optional blocking pad kit
required)
B: Minimum and maximum distance to the floor:
Minimum: 2.5m to avoid accidental touching.
Maximum: Depends on the airflow directions and the capacity
class. See "16.1Field setting"[421].
INFORMATION
Maximum distance to the floor for the 3-way and the 4-way
airflow (which require an optional blocking pad kit) may
differ. See the installation manual of the optional blocking
pad kit.
INFORMATION
Some options may require additional service space. Refer
to the installation manual of the used option before
installation.
12.2 Mounting the indoor unit
12.2.1 Guidelines when installing the indoor unit
INFORMATION
Optional equipment. When installing optional equipment,
also read the installation manual of the optional equipment.
Depending on the field conditions, it might be easier to
install the optional equipment first.
Decoration panel. Install the decoration panel always after
installing the unit.
NOTICE
After installing the decoration panel:
Make sure there is no gap between the unit body and
the decoration panel. Possible consequence: Air
might leak and cause dew drop.
Make sure no oil remains on the plastic parts of the
decoration panel. Possible consequence:
Degradation and damage of plastic parts.
Ceiling strength. Check whether the ceiling is strong enough to
support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.
For existing ceilings, use anchors.
For new ceilings, use sunken inserts, sunken anchors or other
field supplied parts.
A
c
b
d
e
a
A 50~100mm: In case of installation with standard panel
100~150mm: In case of installation with fresh air intake
kit or design panel
130~180mm: In case of installation with auto cleaning
decoration panel
a Ceiling slab
b Anchor
c Long nut or turnbuckle
d Suspension bolt
e Suspended ceiling
Suspension bolts. Use M8~M10 suspension bolts for installation.
Attach the hanger bracket to the suspension bolt. Fix it securely
using a nut and washer from the upper and lower sides of the
hanger bracket.
(mm)
780
710
a1
b
b
a2
c
a1 Nut (field supply)
a2 Double nut (field supply)
b Washer (accessories)
c Hanger bracket (attached to the unit)
Paper pattern for installation (upper part of the packing). Use
the paper pattern to determine the correct horizontal positioning. It
contains the necessary dimensions and centers. You can attach
the paper pattern to the unit.
a cb d
a Centre of the unit
b Centre of the ceiling opening
c Paper pattern for installation (upper part of the packing)
d Screws (accessories)
Ceiling opening and unit:
Make sure the ceiling opening is within the following limits:
Minimum: 860mm to be able to fit the unit.
Maximum: 910 mm to ensure enough overlap between the
decoration panel and the suspended ceiling. If the ceiling
opening is larger, add extra ceiling material.
Make sure the unit and its hanger brackets (suspension) are
centered within the ceiling opening.
(mm)
710
840
860~910
950
c
d
e
f
780
840
860~910
950
c
d
e
f
a
b
a Drain piping
b Refrigerant piping
c Hanger bracket pitch (suspension)
d Unit
e Ceiling opening
f Decoration panel