1. Continuous water flow circulation inside piping and exchangers;
2. Addition of an appropriate amount of glycol inside the water circuit or, as alternative, an additional heat insulation and
heating of exposed piping (internal and external to the unit);
3. If the unit does not work during the winter season, emptying and cleaning of the heat exchanger.
It is the responsibility of the installer and/or of local maintenance personnel to ensure that described antifreeze methods
are used. Make sure that appropriate antifreeze protection is always maintained. Failing to follow the instructions above
could result in unit damage.
4. ELECTRIC HEATER (Option on request). A heater tape is installed on the water side components (the plates heat
exchanger and the expansion vessel) to protect vital parts of the hydraulic system inside the unit. This heater tape will
only protect internal parts of the unit. It cannot protect field installed parts outside the unit. Field heater tapes must be
provided by the installer.(1)
Damage caused by freezing is excluded from the warranty, therefore Daikin Applied Europe S.p.A.
declines all responsibility.
(1) Heat recovery exchanger is not equipped with heater tape.