5 Operation
Operation manual
11
EPVX10+14S(U)18+23A + EPBX10~14A
Daikin Altherma 4 H F+W
4P773378-1 – 2024.11
and the external room thermostat has individual heating/cooling
signals (dual contacts).
To restrict automatic changeover according to a schedule
Conditions: You set the space operation mode to Automatic.
1 Go to [3.5]: Space heating/cooling > Operation mode
schedule.
2 Select a month.
3 For each month, select an option:
Automatic: Not restricted
Heating: Restricted
Cooling: Restricted
4 Confirm the changes.
5.6.2 To change the desired room temperature
During room temperature control, you can use the room temperature
setpoint screen to read out and adjust the desired room temperature.
1 Go to [1.1]: Main zone > Room setpoint.
OR from the home screen: tap on the heat emitter icon of the
zone you want to change.
2 Adjust the desired room temperature:
11:05 21.0°C
Scheduled next
Main zone
Set temperature to…
20
If scheduling is on after changing the desired room temperature
The temperature will stay the same as long as there is no
scheduled action.
The desired room temperature will return to its scheduled value
whenever a scheduled action occurs.
You can avoid scheduled behaviour by (temporarily) turning off
scheduling.
To turn off room temperature scheduling (for heating)
1 Go to [1.2]: Main zone > Heating schedule.
2 Switch scheduling OFF:
Heating schedule
To turn off room temperature scheduling (for cooling)
1 Go to [1.23]: Main zone > Cooling schedule.
2 Switch scheduling OFF:
Cooling schedule
5.6.3 To change the desired leaving water
temperature
INFORMATION
The leaving water is the water that is sent to the heat
emitters. The desired leaving water temperature is set by
your installer in accordance with the heat emitter type.
Only adjust the leaving water temperature settings in case
of problems.
In case no weather-dependent curve is used, you can adjust the
desired leaving water temperature as follows:
For the Main zone without Room thermostat / For the
Additional zone
1 Go to:
[1.1]: Main zone > Leaving water temp.
[2.1] (or [2.30]): Additional zone > Leaving water temp.
OR from the home screen: tap on the heat emitter icon of the
zone you want to change.
2 Adjust the desired leaving water temperature:
11:05 21.0°C
Scheduled next
Main zone
Set temperature to…
35
For the main zone with Room thermostat (i.e. [1.12]= Room
thermostat):
1 Go to [1.39] Leaving water temp
2 Adjust the desired leaving water temperature:
11:05 21.0°C
Scheduled next
Main zone
Set temperature to…
35
5.7 Domestic hot water control
5.7.1 Reheat mode
In reheat mode, the DHW tank continuously heats up to the
temperature shown on the home screen (example: 50°C) when the
temperature drops below a certain value (reheat setpoint [4.5]
hysteresis [4.12]).
t
60°C
00:00 07:00
50°C
15°C
40°C
14:00 21:00
1
2
3
4
T
t
T
t
DHWtank temperature
t Time
INFORMATION
Risk of space heating capacity shortage for domestic hot
water tank without internal booster heater: In case of
frequent domestic hot water operation, frequent and long
space heating/cooling interruption will happen when
selecting Operation mode = Reheat (only reheat
operation allowed for the tank).
To set the DHW Reheat mode
1 Go to [4.7] Domestic hot water > Heat up mode.
2 Set Heat up mode to Reheat.
To change the tank temperature setpoint
In Reheat only and Schedule + reheat mode, you can use the
tank temperature setpoint screen to adjust the domestic hot water
temperature.
1 Go to [4.5]: Tank > Reheat setpoint.