Technician - Electrical connections
Return temperature increase
The return temperature increase function can be activated with pa-
rameter P54 = 6 (storage tank 1; F4) or P54 = 7 (storage tank 2; F2).
The return flow of the heating system is passed through the storage
tank and is heated by it. The system is switched on via A2 when the
temperature in the storage tank has exceeded the temperature of
the return flow (F5) by the switch-on threshold (P32).
The return temperature increase is switched off when the tempera-
ture in the storage tank (F2/F4) drops below the temperature of the
return flow (F5) and the switch-off threshold (P33) (F2/F4 = F5 - P33).
F2/F4
F5
A2/A3
OFF
ON
KF
1
2
2
2
VF