Technician - Electrical connections
System 12 (1 collector, 1 storage tank, 3 feeding areas)
F1
A1
A2
F5
F3
F4
F2
A2
A1
Outputs
A1 Collector pump and storage tank feeding pump
A2 Switch-over valve – lower feeding area
A3 Switch-over valve – central feeding area
Inputs
F1 Collector sensor
F3 Tank top sensor
F4 Tank bottom sensor
F5 Tank centre sensor
Optional
F2 Return sensor for heat volume metering
Switching conditions A1
ON: Temp
F1
- Temp
F4
> P30 and Temp
F1
> P40,
OFF: Temp
F1
- Temp
F4
< P31 or Temp
F1
< P41.
Switching conditions A2
ON: A1 = ON
and Temp
F1
- Temp
F5
> P32 and Temp
F5
< P50 - P32,
OFF: A1 = OFF
or Temp
F1
- Temp
F5
< P33 or Temp
F5
> P50 - P33.
Switching conditions A3
ON: A1 = ON
and Temp
F1
- Temp
F3
> P32 and Temp
F3
< P50 - P32,
OFF: A1 = OFF
or Temp
F1
- Temp
F3
< P33 or Temp
F3
> P50 - P33.