Technician - Electrical connections
System 13 (1 collector, 1 storage tank, drain-back system)
F1
A2
A1
(F2)
F4
F3
Outputs
A1 Collector pump 1
A2 Collector pump 2 for system filling
Inputs
F1 Collector sensor
F3 Storage tank inlet sensor
F4 Storage tank outlet sensor
Optional
F2 Tank top sensor
F5 Additional sensor
Switching conditions A1 and A2
ON: Temp
F1
- Temp
F4
> P30 and TempF1 > P40
and Temp
F1
< P42
and Temp
F4
< P84
OFF: Temp
F2
> P50.
ڀ
In order to fill the collector, the pumps (A1, A2) are
switched on together for the time set with P87. During
filling, the pumps run at the speed set with P107.
Switching conditions A1
At the end of the time set with P87:
ON: Control enable collector pump A1.
OFF: Temp
F3
- Temp
F4
< P31
or Temp
F3
> P85
or Temp
F4
> P86.
Switching conditions A2
OFF: At the end of the time set with P87.
ڀ
Due to the drain-back function, no safety functions (frost
protection, max. collector temperature) are active during standby.