Technician - Electrical connections
System 5 (1 collector, 2 storage tanks, 1 switch-over valve)
A2
F3F5
F4
F2
F1
A1
A3
ON
OFF
A3 A3
Outputs
A1 Collector pump
A2 Switch-over valve to storage tank 2
Optional
A3 Additional relay, function can be freely assigned
Inputs
F1 Collector 1 sensor
F2 Tank bottom 2 sensor
F4 Tank bottom 1 sensor
Optional
F3 Tank top 1 sensor
F5 Tank top 2 sensor
Switching conditions A1
ON: Temp
F1
- Temp
F4
> P30 or Temp
F1
- Temp
F2
> P32
and Temp
F1
> P40,
OFF: Temp
F1
- Temp
F4
< P31 and Temp
F1
- Temp
F2
< P33
or Temp
F1
< P41.
Switching conditions A2
ON: A1 = ON
and Temp
F3
(Temp
F4
, if F3 is not connected) > P50
or Temp
F1
- Temp
F4
< P31
OFF: A1 = OFF
or Temp
F3
(Temp
F4
, if F3 is not connected) < P50 - 5 K,
or Temp
F1
- Temp
F4
> P30