User’s Manual EM11A015H
intelligent Touch Manager
318
<About Demand Function>
If the demand control is not performed for air conditioners even after it is enabled, the possible
causes are the following.
Control group registration and setting up the control for the cut-off levels are not completed.
The cut-off control (i.e. indoor unit setpoint shifting, outdoor unit capacity control, and/or On/Off
control) is not enabled.
The cut-off signal is not input.
We want to change control groups and the control of air conditioners at different cut-off levels.
When should we make such changes?
You should change the settings during a period of time that can minimize the effect of stopping
the demand control. For example, in early morning and midnight.
To change control groups or the control of air conditioners at different cut-off levels, you need
to disable the setpoint shifting, outdoor unit capacity control, and/or On/Off control.
When the control status is set “Disable”, the demand control is not performed.
The indoor unit setpoint shifting is being performed, but the setpoint changes to an unintended
temperature.
Check if somebody changed the setpoint using the remote controller.
If you change the setpoint using the remote controller when the demand control is enabled, the
change overrides the demand control.
So, we recommend you to disable the remote controller if you want to make the best use of the
demand control function.
(See “2-6 Enabling/Disabling Remote Controller”)
24
°C
Setpoint
27
°C
22
°C
+3°C shifting by demand control Set to 22°C by the remote controller (overcooling)
Demand Controlling
13:00 14:00
Possible increase in
power consumption.
Is it possible to use the demand control function and proportional distribution function
simultaneously?
It is possible to use the both functions simultaneously.
However, it requires three Di/Pi ports, so you need to add an iTM plus adaptor/DGE601A52.