Daikin DCM002A51 handleiding
Handleiding
Je bekijkt pagina 320 van 369

User’s Manual EM11A015H
intelligent Touch Manager
319
■
We are currently controlling the ventilators by the iTM. Is it possible to perform the demand
control for them?
• It is possible to stop them by the On/Off control.
■
Is it possible to perform the demand control for the same target device from multiple iTMs?
• It is not an efcient way to use multiple iTMs to perform the demand control for the same target
device.
We recommend you to use one iTM to perform demand control.
■
Is it possible to stop other devices by using contact outputs?
• The demand control allows the On/Off control of devices other than air conditioners via the
contact control products such as: D3Dio, ExternalDio and BACnetDio.
* Be careful not to permit changes from the remote controller when you set up management
points for the D3Dio, ExternalDio and BACnetDio.
■
Is it possible to use the outdoor unit capacity control and the setpoint shifting simultaneously in
the same system?
• It is possible. However, in the case of the following setting for the same cut-off level
Outdoor unit capacity control: 0%
Setpoint shifting: 3°C
the benefit of the setpoint shifting control is not gained, because the outdoor unit will enter a
thermo-OFF state.
Therefore, it is important to consider the relationship between the controls when you design the
demand control settings.