4 Unit installation
Installation manual
8
EPSK06~14A
Daikin Altherma 4 H
4P773384-1 – 2024.08
4 Unit installation
4.1 Preparing the installation site
WARNING
The appliance shall be stored in a room without ignition
sources (neither permanent ignition sources nor ignition
sources for a short period of time) (example: open flames,
an operating gas appliance or an operating electric heater).
WARNING
The appliance shall be installed in an area without ignition
sources (neither permanent ignition sources nor ignition
sources for a short period of time) (example: open flames,
an operating gas appliance or an operating electric heater).
WARNING
Make sure installation, servicing, maintenance and repair
comply with instructions from Daikin and with applicable
legislation (for example national gas regulation) and are
executed ONLY by authorised persons.
4.1.1 Installation site requirements of the
outdoor unit
The outdoor unit is designed for outdoor installation only, and for the
following ambient temperatures:
Cooling mode 10~43°C
Heating mode –28~25°C
Domestic hot water production Up to 40°C
Make sure to comply with the following guidelines:
▪ Choose an installation location with sufficient space.
▪ Do NOT install the unit in locations often used as work location.
▪ Do NOT install the unit in locations near a road or parking area
where it can be damaged by passing traffic.
▪ Do NOT install the unit in a basement.
▪ Do NOT install the unit in sound sensitive areas (e.g. near a
bedroom), so that the operation noise will cause no trouble. Note:
If the sound is measured under actual installation conditions, the
measured value might be higher than the sound pressure level
mentioned in Sound spectrum in the data book due to
environmental noise and sound reflections.
▪ Do NOT install the unit in locations where a mineral oil mist, spray
or vapour may be present in the atmosphere. Plastic parts may
deteriorate and fall off or cause water leakage.
Spacing guidelines. There are two sets of spacing guidelines:
▪ Service space: See Figure 1 at the beginning of this manual.
Legend:
General Multiple outdoor units can be installed next to each
other as shown in the rows:
▪ (side-to-side)
▪ (front-to-front / back-to-back)
However, other units may only be installed in your unit's
protective zone if they are of the same type (see
"protective zone").
A, C Right side and left side obstacles (walls/baffle plates)
B Suction side obstacle (wall/baffle plate)
D Discharge side obstacle (wall/baffle plate)
E Top side obstacle (roof)
a,b,c,d,e Minimum service space between the unit and obstacles
A, B, C, D and E
e
B
Maximum distance between the unit and the edge of
obstacle E, in the direction of obstacle B
e
D
Maximum distance between the unit and the edge of
obstacle E, in the direction of obstacle D
H
U
Height of the unit including the installation structure
H
B
,H
D
Height of obstacles B and D
NOT allowed
▪ Protective zone: See Figure 2 and Figure 3 at the beginning of
this manual. Legend:
General The outdoor unit contains R290 refrigerant, which
belongs to "Safety class A3" as defined in ISO817 and
used in EN378. This means that you must comply with
extra installation site requirements (="protective zone")
to ensure safety in the unlikely event of a refrigerant
leak.
Required for the protective zone:
▪ No openings into habitable areas of the building.
Example: openable windows, doors, ventilation
openings, or basement entrances.
▪ No ignition sources (neither permanently nor for a
short period of time). Example:
▪ Open flames
▪ Electrical installations, sockets, lamps, light
switches
▪ Electrical house connections
▪ Sparking tools
▪ Objects with high surface temperatures (>360°C
for R290)
▪ The protective zone must NOT extend to adjacent
buildings or public traffic areas.
▪ Other units may only be installed in your unit's
protective zone if they are of the same type (i.e.
EPSK). So, units of a different type, using a different
refrigerant, or from another manufacturer are NOT
allowed in your unit's protective zone. The combined
protective zone of all units is then the addition of all
individual protective zones.
NOT required for the protective zone:
▪ Complete open area in front of the unit.
1a / 1b Protective zone in front of a building:
▪ 1a: on floor
▪ 1b: elevated
2a / 2b Protective zone for right corner installation:
▪ 2a: on floor
▪ 2b: elevated
3a / 3b Protective zone for left corner installation:
▪ 3a: on floor
▪ 3b: elevated
4 Protective zone for on-roof installation.
Extra requirement: No ventilation or skylight openings
in the protective zone.