4 Unit installation
Installation manual
9
EPSK06~14A
Daikin Altherma 4 H
4P773384-1 – 2024.08
4.2 Mounting the outdoor unit
4.2.1 To provide the installation structure
NOTICE
Level. Make sure the unit is leveled in all directions.
Recommended:
Use 4 sets of M12 anchor bolts, nuts and washers. Provide at least
150 mm of free space below the unit. Additionally, make sure the
unit is positioned at least 100 mm above the maximum expected
level of snow.
Anchor points + drain hole
a
830
615.7
(mm)
a Drain hole
Pedestal
830
615.7
a
≥150
(mm)
M12
a Make sure not to cover the drain hole in the bottom plate
of the unit.
4.2.2 To install the outdoor unit
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium
fins of the unit.
1 Carry the unit by its slings, and put it onto the installation
structure.
EPSK06~10AV3
EPSK08~10AW1
EPSK12~14
±175 kg
±180 kg
±190 kg
kg
2 Fix the unit to the installation structure.
M12
3 Remove the slings (+ clips + pins), and dispose of them.
2
1
3