2 — INSTALLATION AND WIRING
Curtis Model 1226BL – July 2024 Return to TOC
pg. 18
Valve Input
You can use either of the analog/digital inputs as a valve input. To do so, set the inputs Type parameter to 1 (Lower
Valve Input). e menu containing the Type parameter to set depends upon which pin is used for the valve:
Pin J3-6 = Digital/Analog 1 menu
Pin J3-4 = Digital/Analog 2 menu
Note: If the vehicle has 2 lower valve switches on the tiller head, specify Lower Valve Input for the Type
parameters on both the Digital/Analog Input 1 and Digital/Analog Input 2 menus. With that conguration,
if the operator presses either or both switches the controller will engage the driver to lower the fork.
Emergency Reverse Inputs
When emergency reverse is activated, the controller produces a rapid braking force to stop the vehicle, then
slowly drives the vehicle in the opposite direction.
Emergency reverse can be activated by a Normally Open (NO) switch, a Normally Closed (NC) switch, or
both NO and NC switches used as complementary switches. Use the EMR Input Type parameter to specify
the switch(es).
e following pins are used for NO and NC switches:
NO switch: J3-14
NC switch: J3-4
Note: If the vehicle system doesn't use an NC switch for emergency reverse, you can use pin J3-4 as the Analog
2/Digital 2 input. See Digital Inputs.
When complementary switches are used for emergency reverse, the controller continually checks both
switches for conditions such as shorts and broken connections.
Use the Emergency Reverse Menu to congure features such as those in the following list:
Whether the operator can activate emergency reverse while driving in reverse.
How long the vehicle will operate while an emergency reverse switch is active.
e rate at which the vehicle decelerates to a stop.
e rate at which the vehicle accelerates in the reverse direction.
Note: e controller checks for the EMR SRO and EMR HPD faults.
Belly Button Switch
The controller provides a belly button check function that monitors the emergency reverse circuit for
continuity. If no continuity is detected, the controller issues the HARDWARE FAULT fault (fault type 3) and
shuts down the controller.
To use the belly button check, connect a wire from the pot high input (pin J3-16) to the emergency reverse
NC switch (pin J3-4). e function is enabled with the BB Check Enable parameter.
If the belly button check is enabled, the following considerations apply:
Pin J3-4 must be used only for the emergency reverse NC switch.
e Digital Input Low reshold parameter must be set to 13.00V.
e Digital Input High reshold parameter must be set to 15.00V.