27
ENG
iJW +0300103EN rel. 1.1 - 31.03.2025
Index
6. INITIAL CONFIGURATION
Once the electrical connections have been completed (see “Installation”) and the power supply has been connected, the oper-
ations required for commissioning the controller depend on the type of interface used, however essentially involve setting the
initial confi guration parameters and where necessary the date/time and the time bands. The parameter confi guration procedure
can be run on the user terminal, a mobile device (with the Applica app), or the Applica Desktop confi guration software. The
parameters used for commissioning are shown in the Parameter table.
Caution:
the parameters that can be set on the user terminal and in the Applica app may vary according to the rights assigned to the
access profi le, defi ned by the manufacturer. Therefore, not all of the following parameters may be visible or modifi able.
Some operations can only be performed using Applica or the Applica Desktop confi guration software, for example, confi gur-
ing the display during defrost or setting the date/time and time bands.
Initial confi guration parameters
Par. Menu Desc. Def. Min Max UOM User
St Ctl Temperature control set point 50 r1 r2 °C/°F U
/5 Pro Unit of measure: 0 = °C; 1 = °F 0 0 1 - U
/6 Pro Display decimal point (main screen only): 0 = visible; 1 = not visible 0 0 1 - S
/t1 Pro Display on user terminal:
0 = Not confi gured 4 = value of S4 10 = virtual probe
1 = value of S1 5 = value of S5 11 to 14 = not available
2 = value of S2 6 to 8 = not available 15 = actual control set point
3 = value of S3 9 = control probe
10 0 16 - S
d6 - Display during defrost: 0 = temperature alternating with dEF; 1 = freeze display; 2 = dEF 1 0 2 - S
dI dEF Maximum interval between defrosts 8 0 240 h S
dP1 dEF Maximum defrost duration 45 1 240 min S
AH ALM Relative high temperature alarm threshold 0 0 555/999 Δ °C/°F S
AL ALM Relative low temperature alarm threshold 0 0 200/360 Δ °C/°F S
Hb CnF Enable buzzer: 0 = disabled; 1 = enabled 1 0 1 - U
/P1 Pro Confi guration of probes S1, S2, S3, S4, B5 0 = PT1000; 1 = PTC; 2 = NTC; 3 = NTC-LT; 4 = NTC-HT 2 0 4 - S
/P2 Pro Confi guration of multifunction input S3/ DI1: 0, 1, 2, 3, 4 = S3; 5 = DI1. 5 0 5 - S
(*): U = User; S = Service.
6.1 Description of the initial con guration parameters
St: temperature control set point
Parameter St is used to set the temperature control set point.
Par. Menu Desc. Def. Min Max UOM User
St Ctl Temperature control set point 50/122 r1 r2 °C/°F U
rd: temperature control diff erential
Parameter rd is used to set the temperature control diff erential (see “Control”).
Par. Menu Desc. Def. Min Max UOM User
rd Ctl Temperature control diff erential 2.0/3.6 0.1/0.2 99.9/179.2 Δ °C/°F S
/5, /6, /t1: display on user terminal
Parameters /5, /6 and /t1 are used to set the display shown on the user terminal. Parameter /5 sets the unit of measure °C or °F,
parameter /6 sets whether or not the decimal digit is displayed and parameter /t1 sets the value displayed, either the control
probe or virtual probe reading, or one of the set points. By default, the virtual control probe value is displayed, expressed in °C
with one decimal.
Par. Menu Desc. Def. Min Max UOM User
/5 Pro Unit of measure: 0 = °C; 1 = °F 0 0 1 - U
/6 Pro Display decimal point (main screen only): 0 = visible; 1 = not visible 0 0 1 - S
/t1 Pro
Display on user terminal:
0 = Not confi gured 4 = value of S4 10 = virtual probe
1 = value of S1 5 = value of S5 11 to 14 = not available
2 = value of S2 6 to 8 = not available 15 = actual control set point
3 = value of S3 9 = control probe
9 0 15 - S
d6: display on user terminal during defrost
Parameter d6 is used to set the display shown on the user terminal when defrosting, chosen between the value selected by
parameter /t1 alternating with the message dEF’, the last value shown before defrosting, or dEF’ alone on steady. If d6 =1, the
normal display resumes when the control temperature reaches the set point, the temperature displayed is lower than the value
locked on the display or, in any case, after the time set for “bypass alarm after defrosting (d8). By default, the value displayed
before defrosting is shown (d6=1).
Par. Menu Desc. Def. Min Max UOM User
d6 - Display during defrost: 0 = temperature alternating with dEF; 1 = display locked; 2 = dEF 1 0 2 - S