Channe
l
Type
Description
ff
10 (Reboot)
ff (Reserved)
03 (Set Reporting Interval)
2 Bytes, unit: s
02 (Set Collecting Interval)
2 Bytes, unit: s
06 (Set Threshold Alarm)
9 Bytes,
CTRL(1B)+Min(2B)+Max(2B)+00000000(4B)
CTRL:
Bit2~Bit0:
000=disable
001=below
010=above
011=within
100=below or above
Bit5~Bit3: ID
001=Temperature Threshold
010=Temperature Mutation Threshold
Bit6:
0=disable the Alarm Threshold
1=enable the Alarm Threshold
Bit7: Reserved
68 (Data Storage)
00: disable, 01: enable
69 (Data Retransmission)
00: disable, 01: enable
6a (Data Retransmission
Interval)
3 Bytes
Byte 1: 00
Byte 2-3: interval time, unit:s
range: 30~1200s (600s by default)
Example:
1. Set reporting interval as 20 minutes.
ff03b004
Channel
Type
Value
ff
03 (Set Reporting Interval)
b0 04 => 04 b0 = 1200s = 20 minutes