Channel
Type
Value
03
67
(Temperature)
52 01 => 01 52 => 338*0.1 = 33.8°C
2. Temperature Mutation Alarm Packet
83d722010c0002
Channel
Type
Value
83
d7
(Temperature Mutation
Threshold)
Temperature: 22 01 => 01 22 => 290*0.1
= 29°C
Mutation Value: 0c 00 => 00 0c =>
12*0.1=1.2°C
02 => Mutation Alarm
5.2 Downlink Command
Downlink is used for controlling the LEO-S572-C2G0 via network server remotely. Downlink
port (Application port) is 85 by default and can be configured via ToolBox.
Note: only device with hardware V2.x and later supports below commands.
Channe
l
Type
Description
ff
03 (Reporting Interval)
2 Bytes, unit: s
10 (Reboot)
ff (Reserved)
17 (Time Zone)
2 Bytes, UTC timezone * 10
18 (Sensor Collection)
Sensor Type (1B) + Status (1B)
Status: 00: disable, 01: enable
Sensor Type:
00: all
01: temperature
02: humidity
05: CO
2
06: barometric pressure
1a (CO
2
Calibration)
00: Factory Calibration Restored
03: Manual Calibration
39 (CO
2
Auto Background
Calibration)
5 Bytes,
Byte 1: 00-disable, 01-enable
Bytes 2-5: b4009001
68 (Data Storage)
00: disable, 01: enable