Advantech LEO-S573-C2 handleiding
Handleiding
Je bekijkt pagina 21 van 25

www.advantech.com
21
21
1. First sensor data packet after join: report battery level + sensor data
2. Periodic packet: report sensor data according to reporting interval (10 min by default)
3. Battery level packet: every 24 hours or when battery level is lower than 10%
4. Normal threshold alarm: report the sensor data when reaching the threshold
Sensor
Type ID
(hex)
Data Type
Data
Resolution
Temperature
67
INT16
0.1 °C
Humidity
68
UINT8
0.5 %RH
Barometric Pressure
73
UINT16
0.1 hPa
Battery
75
UINT8
1 %
Concentration
7d
UINT16
1 ppm
Examples:
017564 03671001 046871 057d6704 06736827
Channel
Type
Data
Channe
l
Type
Data
01
75
(Battery)
64 =>
100%
03
67
(Temperature)
10 01=>01 10
=272*0.1=27.2°
C
Channel
Type
Data
Channe
l
Type
Data
04
68
(Humidity)
71=>113*0
.5=56.5%
05
7d (CO
2
)
67 04 => 04 67
=1127 ppm
Channel
Type
Data
06
73
(Barometric
Pressure)
68 27=>27
68=10088*
0.1=1008.
8 hPa
5.1.3 Temperature Mutation Threshold
LEO-S573-C2G0 supports to report temperature mutation threshold alarm which has a
different format with normal threshold alarm.
Channel
Type
Description
83
d7 (Mutation
Threshold Alarm)
Temperature(2B) + Mutation Value(2B) + 02
Example:
1. Normal Temperature Threshold Alarm Packet
03675201 01