Advantech LEO-S573-C2 handleiding

25 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 23 van 25
www.advantech.com
23
23
69 (Data Retransmission)
00: disable, 01: enable
6a (Data Retransmission
Interval)
3 Bytes
Byte 1: 00
Byte 2-3: interval time, unit:s
range: 30~1200s (600s by default)
Example:
1. Configure Reporting Interval as 20 mins
ff 03 b0 04
Channel
Type
Data
ff
03(Set Reporting Interval)
b0 04 => 04 b0 = 1200s=20
mins
2. Reboot the device.
ff10ff
Channel
Type
Value
ff
10 (Reboot)
ff (Reserved)
3. Set the time zone as UTC-2.
ff17ecff
Channel
Type
Value
ff
17
ec ff => ff ec = -20
the time zone is UTC-2
4. Disable humidity collection
ff180200
Channel
Type
Value
ff
18
02=Humidity, 00=Disable
5.3 Historical Data Enquiry
LEO-S572-C2G0 support sending downlink commands to enquire historical data for specified
time point or time range. Before that, ensure the device time is correct and data storage
feature was enabled to store the data.
Command format:
Channel
Type
Description
fd
6b (Enquire data in time point)
4 Bytes, unix timestamp
fd
6c (Enquire data in time range)
Start time (4 bytes) + End time (4 bytes),
Unix timestamp