Advantech ADAM-4150 handleiding
Handleiding
Je bekijkt pagina 19 van 144

11 ADAM-4100 User Manual
Chapter 2 Installation Guide
Figure 2.3 Ground Connector on an ADAM-4117
2.2.3 Module Configuration with the Adam/Apax .NET Utility
The easiest way to configure ADAM modules is by the /Apax .NET Utility. It is a user-
friendly structured program that will guide you through every step of the configuration
(see Appendix A)
2.2.4 Changing the Protocol from ADAM ASCII to Modbus
Some ADAM-4100 modules support both ADAM ASCII and Modbus protocols. By
default, these modules are set to the ADAM ASCII protocol. Refer to Appendix G for
information on switching your modules to the Modbus protocol.
2.2.5 Module Configuration with the ADAM Command Set
ADAM modules can also be configured by issuing direct commands through a termi-
nal emulation program that is part of the Adam/Apax .NET Utility (refer to Chapter 4).
2.2.6 Communication via Micro USB
The USB interface has become common in IoT devices. Furthermore, it makes
access by laptop or PC easy. To expand the accessibility of ADAM-4100 series mod-
ules, other than the RS-485 serial port, ADAM-4100 series modules (B version) fea-
ture a micro USB interface. Modules can be powered on and communicate through
this interface. When a module is communicating via RS-485, the USB can also be
used at the same time for communication. You can choose either the micro USB or
RS-485 interface to access the modules.
Note! The baud rate of micro USB and RS-485 will be identical for the mod-
ules; this means that if the RS-485 or USB baud rate is changed, the
other one will automatically align to the same baud rate.