2.3 I Electrical connecons
2.3.1 Voltage and protecon
The power supply to the heater must be provided through a protecon and circuit breaking device (not
supplied) complying with the standards and regulaons in force in the country where it is installed,
The electrical connecon lines must be xed,
Use the gland to pass the power cord into the appliance.
Electrical protecon: via a dedicated 30 mA residual-current circuit breaker (circuit breaker or switch)
Acceptable variaon in voltage: ± 10% (during operaon)
2.3.2 Connecons
Incorrectly ghtened terminals may cause the terminal unit to heat up and invalidate the
warranty.
The appliance must be connected to an earth socket.
Risk of electrical shock inside the appliance.
Only a qualied and experienced technician is authorised to carry out cabling in the appliance.
If the power cord is damaged, it must be replaced by a qualied technician.
The power cord must be insulated against any cung or hot elements that may damage or crush it,
Check that the power cord is rmly aached to the connecon terminal board.
12 kW Red Line units are wired via three-phase systems only.
3, 6 and 9 kW Red Line units are pre-wired for supply via a single-phase system when leaving the
factory.
To switch to a three-phase supply:
- Detach the label from the terminal block,
- Remove the 2 bridging straps ( ),
- Reaach the label aer pivong it by 180° from its original posion.
Single-phase
: Heater terminal block
Three-phase
: Bridging straps
: Power cord
: 30mA residual-current
circuit breaker
: Phase
: Neutral
: Earth
2.3.3 Cable sizes
Power cord size: for cables of a maximum length of 20 metres (calculaon basis: 5A/mm²), this must be
checked and adapted depending on the installaon condions.
Red Line Voltage
Bridging
straps
Terminals
Power
consumed
Cable size
Protecon
rang
A mm² A
3
230V/1N/50Hz R-S-T C-N 14 3x4 3G4 16
400V/3N/50Hz / 5 5x2.5 5G2.5 10
6
230V/1N/50Hz R-S-T C-N 27 3x6 3G6 32
400V/3N/50Hz / 9 5x2.5 5G2.5 16
9
230V/1N/50Hz R-S-T C-N 40 3x10 3G10 50
400V/3N/50Hz / 13 5x4 5G4 16
12 400V/3N/50Hz / 18 5x4 5G4 20