18
The appliance
is working
but the water
temperature
does not increase
Check that the automac water lling controller (see diagram in § "2.3 I Operaon") is not
stuck in the open posion: this will keep supplying cold water into the pool and will prevent the
temperature from rising.
There is too much heat loss: install a heat insulated cover on your pool.
The heat pump is unable to capture enough calories as its evaporator is clogged with dirt: clean
it to restore its eciency (see § “3.2 I Servicing”).
Check that the external environment is not hindering the heat pump (see § “❶ Installaon”).
Check that the heat pump is the right size for this pool and its environment.
The fan is
running but
the compressor
stops from me
to me with no
error message
If the outdoor temperature is low, the heat pump performs defrost cycles under normal
operaon.
The heat pump is unable to capture enough calories as its evaporator is clogged with dirt. Clean
it to restore its performances (see § “3.2 I Servicing”).
The appliance
trips the circuit
breaker
Check that the circuit breaker is correctly dimensioned and that the cable secon used is
appropriate (see § “5.2 I Technical specicaons”).
The supply voltage is too low: contact your electricity supplier.
4.2 I Error code display
Display Possible causes Soluons
PP01
Faulty inlet water temperature sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP02
Faulty outlet water temperature sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP03
Faulty coil temperature sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP04
Faulty discharge gas temperature sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP05
Faulty ambient temperature sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP06
Faulty cooling condenser sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP07
Winter frost protecon
Ambient temperature or input water
temperature too low.
Check D3 and D1.
PP08
Ambient temperature protecon too low
The ambient temperature is too low.
Check D3.
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP10
Condenser cooling temperature too high
protecon
Ambient temperature too high Check the temperature.
Refrigerant problem
Check the refrigerant.
PP11
Water temperature too cold protecon in
cooling mode
Water ow too low
Check the water ow rate and by-
pass.
Abnormal temperature of d2-TH5
sensor
Check the refrigerant and d2-TH5
sensor.
EE01
High pressure protecon
Ambient temperature too high.
Check the water ow rate and by-
pass.
Water temperature too high.
Check the fan.
Check the fan speed.
Check the refrigerant.
EN