The appliance
is working
but the water
temperature
does not increase
• Check that the automac water lling controller (see diagram in § "2.3 I Operaon") is not
stuck in the open posion: this will keep supplying cold water into the pool and will prevent the
temperature from rising.
• There is too much heat loss: install a heat insulated cover on your pool.
• The heat pump is unable to capture enough calories as its evaporator is clogged with dirt: clean
it to restore its eciency (see § “3.2 I Servicing”).
• Check that the external environment is not hindering the heat pump (see § “❶ Installaon”).
• Check that the heat pump is the right size for this pool and its environment.
The fan is
running but
the compressor
stops from me
to me with no
error message
• If the outdoor temperature is low, the heat pump performs defrost cycles under normal
operaon.
• The heat pump is unable to capture enough calories as its evaporator is clogged with dirt. Clean
it to restore its performances (see § “3.2 I Servicing”).
The appliance
trips the circuit
breaker
• Check that the circuit breaker is correctly dimensioned and that the cable secon used is
appropriate (see § “5.2 I Technical specicaons”).
• The supply voltage is too low: contact your electricity supplier.
4.2 I Error code display
Display Possible causes Soluons
PP01
Faulty inlet water temperature sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP02
Faulty outlet water temperature sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP03
Faulty coil temperature sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP04
Faulty discharge gas temperature sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP05
Faulty ambient temperature sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP06
Faulty cooling condenser sensor
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP07
Winter frost protecon
Ambient temperature or input water
temperature too low.
Check D3 and D1.
PP08
Ambient temperature protecon too low
The ambient temperature is too low.
Check D3.
Sensor disconnected or out of order.
Reconnect or replace the sensor.
PP10
Condenser cooling temperature too high
protecon
Ambient temperature too high Check the temperature.
Refrigerant problem
Check the refrigerant.
PP11
Water temperature too cold protecon in
cooling mode
Water ow too low
Check the water ow rate and by-
pass.
Abnormal temperature of d2-TH5
sensor
Check the refrigerant and d2-TH5
sensor.
EE01
High pressure protecon
Ambient temperature too high.
Check the water ow rate and by-
pass.
Water temperature too high.
Check the fan.
Check the fan speed.
Check the refrigerant.
EN