Zodiac HPO handleiding
Handleiding
Je bekijkt pagina 17 van 28

16
• If a leak is suspected, all naked ames must be removed/exnguished.
• If a refrigerant leak is detected and requires soldering, the enre quanty of refrigerant must be removed from the
system or isolated (by way of shut-o valves) in part of the system located away from the leak.
Removal and discharge
• When accessing the cooling circuit to carry out repairs, or for any other reason, convenonal procedures must be
employed. However, for ammable refrigerants, the recommendaons must be complied with in order to take
account of the product's ammability. The following procedure must be followed:
- remove the refrigerant;
- purge the circuit with an inert gas (oponal for A2L);
- drain (oponal for A2L);
- purge with an inert gas (oponal for A2L);
- open the circuit by cung or soldering.
• The refrigerant charge must be recovered in suitable recovery cylinders. For appliances containing ammable
refrigerants other than A2L refrigerants, the system must be bled with nitrogen devoid of oxygen to make the appliance
suitable for receiving ammable refrigerants. You may need to repeat this process several mes. Compressed air or
oxygen must not be used to purge cooling systems.
Loading procedures
• Check that the vacuum pump outlet is not located in the vicinity of any potenal ignion source and that venlaon
is provided.
• In addion to convenonal charging procedures, the following requirements apply.
- Check that there is no possibility of cross-contaminaon between the dierent refrigerants when using charging
equipment. Hoses or lines must be as short as possible to reduce the quanty of refrigerant contained therein.
- Cylinders must be kept in an appropriate posion, in accordance with the instrucons.
- Check that the cooling system is grounded before charging the system with refrigerant.
- Label the system once charging is complete (if this is not already the case).
- Pay close aenon to not overlling the cooling system.
• Before recharging the system, carry out a pressure test using a suitable purge gas. The system must be examined to
make sure there are no leaks aer the charging operaon and before commissioning. A follow-up leak test must be
carried out before leaving the site.
Dismantling
• Before dismantling, the technician must familiarise himself/herself with the equipment and its specicaons. We
highly recommend carefully recovering all refrigerants. Before this, oil and refrigerant samples must be taken if
analyses are to be carried out before any other use of the recovered refrigerant. Check for the presence of a power
supply before starng work.
1. Familiarise yourself with the equipment and how it operates.
2. Electrically isolate the system.
3. Before starng work, check the following points:
- mechanical handling equipment is available if needed to handle the refrigerant cylinders;
- all personal protecve equipment is available and used correctly;
- the recovery process is monitored at all mes by a cognisant person;
- the recovery cylinders and equipment comply with the relevant standards.
4. Drain the cooling system where possible.
5. If a vacuum cannot be created, install a manifold in order to be able to remove the refrigerant from various locaons
within the system.
6. Make sure that the cylinder is located on the scales before starng recovery operaons.
7. Start the recovery unit and operate as per its instrucons.
8. Do not overll the cylinders (no more than 80% of the volume must be lled with liquid).
9. Do not exceed the maximum working pressure of the cylinder, even temporarily.
10. When the cylinders have been lled correctly and the process is complete, check that the cylinders and the
equipment are quickly removed from the site and that the alternave shut-o valves on the equipment are closed.
11. The recovered refrigerant must not be charged in another cooling system, unless it has been cleaned and inspected.
EN
Bekijk gratis de handleiding van Zodiac HPO, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Zodiac |
| Model | HPO |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 6991 MB |







