Zodiac Heat Line handleiding
Handleiding
Je bekijkt pagina 14 van 17

13
❺ Troubleshoong
• Before you contact the retailer, carry out these few simple checks using the following tables
if a problem occurs.
• If the problem is not resolved, contact your retailer.
• : Acons to be performed by a qualied technician only
5.1 I Appliance behaviour
The appliance
does not start
heang straight
away
• When the setpoint temperature is reached, the appliance stops heang: the water temperature
is higher than or equal to the setpoint temperature.
• When the water ow rate is zero or is not enough, the appliance stops: check that the water is
circulang correctly in the exchanger and that the hydraulic connecons are correct.
• The appliance may have detected an operang fault (see § « 5.2 I Error code display »).
• If you have checked these points and the problem persists: contact your retailer.
The appliance is
not working
• If there is no display, check the supply voltage and the fuse. If necessary, replace it (see §
« 5.3 I Replacing the switch box fuse (depending on the model) »).
• When the setpoint temperature is reached, the appliance stops heang: the water temperature
is higher than or equal to the setpoint temperature.
• When the water ow rate is zero or is not enough, the appliance stops: check that the water is
circulang correctly in the appliance.
• The appliance may have detected an operang fault (see § « 5.2 I Error code display »).
The appliance
is working
but the water
temperature does
not increase
• The appliance may have detected an operang fault (see § « 5.2 I Error code display »).
• Check that the automac lling valve is not stuck in open posion; this will keep supplying cold
water into the pool and will prevent the temperature from rising.
• There is too much heat loss as the air is cool. Install a heat insulated cover on your pool.
• Check that the appliance is the right size for this pool and its environment.
There is noise in
the circuit
• Idenfy whether the noise is coming from the circuit or the circulang pump.
• If the noise is coming from the circuit:
- Air is trapped in the circuit: purge the installaon.
- The water ow rate is too high; reduce the operang speed: (see § « 3.4.2 Operaon of the
circulang pump on Heat Line Plus »).
• If the noise is coming from the circulang pump:
- There is air in the circulang pump; let it run. It will bleed itself.
- The water ow is too low: increase the pressure in the primary circuit and/or check the air
volume in the expansion chamber (if installed).
The pool water
is hoer than
requested
• The circulang pump is not operang correctly: Check that it stops when the setpoint
temperature is reached.
• Another circulang pump is pushing on the primary circuit: provide a solenoid valve on the
outlet of the primary circuit managed by terminals 19-20 (see § « 2.3.1 Connecng an external
command to supply the primary circuit »).
The appliance
trips the circuit
breaker
• Check that the circuit breaker is correctly dimensioned and that the cable secon used is
correct (see § « 1.2 I Technical specicaons »).
• The supply voltage is too low; contact your electricity supplier.