Zodiac CAE Ducted handleiding
Handleiding
Je bekijkt pagina 9 van 26

H03846‐00.A1.EN–2012/10 8
2.6.4HygroControlconnection
Hygro Control = digital display hygro‐thermostat = display and setting of pool hall temperature* and
humidity
- forinstallationlocation:see§2.2,§2.3,§2.4andreferto§2.1,
- correctlyinfl uencedbytheswimmingpoolroomair,
- connecttoterminalsontheelectricbox.
Mainssupply12Vac‐50Hz‐betweenterminals4and5,
Thenumberingoftheterminalsmustberespected,
Donotputthesecablesintothesameductasother230Vor400Vtoavoidanyriskofinterferenceof
thesignals,
Obstruct the place where the cable emerges from the wall or seal it by using materials other than
siliconeandsilicone‐basedmaterials,inordertoavoidanyarrivalofairexteriortotheroomthrough
theductordividingwall.
Technicalspecifications
Admissibleroomtemperature °C 0‐55
Admissiblehumiditylevel % 0‐90
Voltage Vac 12
Maximumvoltage Vac 24
Protectionindex IP 20
Dimensions:width/height/depth mm 120x70x28
Hysteresis
Humidity % 4
temperature °C 1
Display
Option Voltage
Nominal
power
consumption
Maximum
power
consumption
Cablesize
Unit A A mm²
Omega20
withoutoptionorhotwaterbattery 400V‐50Hz‐ 16.4 20.1 5x4 5G4
Extraheating18kW 400V‐50Hz‐ 42.4 49 5x10 5G10
Omega28
withoutoptionorhotwaterbattery 400V‐50Hz‐ 19 23.8 5x6 5G6
Extraheating18kW 400V‐50Hz‐ 45 53 5x16 5G16
Cable5x1mm²,
maximumlength:30meters
“on/off”
GeneralCAEorOmégaterminals
Temperature* and humidity programming
orhygro‐thermostatsettings
valuessetting
Temperaturedisplay*
RelativeHumidity
Degrees Fahrenheit
Degrees Celsius
Requesting
dehumidification
Requestingheating