H03846‐00.A1.EN–2012/10 7
2.6Electricalconnections
2.6.1Voltageandprotection
The electrical supply must be provided through a protection and circuit breaking device (not supplied)
complyingwiththestandardsandregulationsinforceinthecountrywhereitisinstalled,
Electricalprotection:30mAgroundfaultcircuitbreaker.
Acceptablevoltagevariationtolerance:±10%(duringoperation),
Electriccablesmustbefixed,
2.6.2Connections
Looseterminalsmaycausethesupplyterminalboardtooverheat,andwillvoidthewarranty.
Theappliancemustbeearthed.
Riskofelectricalshockinsidethedevice. Onlyaqualifiedandexperiencedtechnicianmustinstallthe
devicecables.Ifthepowercableisdamageditmustbereplacedbyaqualifiedtechnician.
2.6.3Cablesizes
Supply cable size: for cables of a maximum length of 20 metres (calculation basis: 5A/mm²), this must be
checkedandadapteddependingoninstallationconditions.
Option Voltage
Nominal
power
consumption
Maximum
power
consumption
Cablesize
Unit A A mm²
CAE508
Single‐
phase
withoutoptionorhotwaterbattery 230V‐50Hz‐ 17.5 37.1 3x6 3G6
Extraheating4.5kW 230V‐50Hz‐ 32.7 48.5 3x10 3G10
CAE508
three‐
phase
withoutoptionorhotwaterbattery 400V‐50Hz‐ 5.3 8 5x2.5 5G2.5
Extraheating9kW 400V‐50Hz‐ 18.5 22.5 5x6 5G6
CAE510
three‐
phase
withoutoptionorhotwaterbattery 400V‐50Hz‐ 8.5 14.5 5x4 5G4
Extraheating9kW 400V‐50Hz‐ 21.5 29 5x6 5G6
Extraheating18kW 400V‐50Hz‐ 34.5 43.5 5x10 5G10
CAE513
three‐
phase
withoutoptionorhotwaterbattery 400V‐50Hz‐ 11 17 5x4 5G4
Extraheating9kW 400V‐50Hz‐ 24 31.5 5x10 5G10
Extraheating18kW 400V‐50Hz‐ 37 46 5x10 5G10
Omega10
withoutoptionorhotwaterbattery 400V‐50Hz‐ 7.6 13 5x2.5 5G2.5
Extraheating9kW 400V‐50Hz‐ 20.6 27.5 5x6 5G6
Omega14
withoutoptionorhotwaterbattery 400V‐50Hz‐ 9 16 5x4 5G4
Extraheating9kW 400V‐50Hz‐ 22 30.5 5x6 5G6
Omega16
withoutoptionorhotwaterbattery 400V‐50Hz‐ 12 18.5 5x4 5G4
Extraheating18kW 400V‐50Hz‐ 38 47.5 5x10 5G10
Alimentation
Regulation
(HygroControl)
CAEsingle‐
phase
:230Vac‐50Hz
:contact(230Vac‐50Hz‐5Amaximum)
Circulatorconnectionor
controlofheatsource
Connectionofauxuiliary
pumporfilterclock
Hotwater
batter
y
o
p
tion
Mainsupply
230Vac‐50Hz‐
forremotefault
warninglight
Watercondenser
option
Bekijk gratis de handleiding van Zodiac CAE Ducted, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Zodiac |
Model | CAE Ducted |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 6812 MB |