H03846‐00.A1.EN–2012/10 5
*
minimumdistancerearviewoftheCAE(throughthewall)
Dimensionsinmm,indicationsofvaluesforinstallationusingaccessoriesforaCAEwith mini‐ductnetwork(see
ZodiacPoolCareEuropecatalogue).
CAE508‐510‐513
suction
blowing
soundtrap
blowerelbow
doubledeflectorgrate
2.4Connectiontoaductnetwork
Installtheapplianceinatechnicalroomthatisprotectedfromfreezing.
Connecttheintakeandblowerduct(orstandardparts)respectingtheaircircula tiondirection:
Framedimensions
Minimumcross‐sectionfor
blowerandintakeducts
Appliance Unit
intake Blowing
Rectangular Circular
behind left‐ right Front‐rear‐top upper
CAE508 mm 825x405 559x465 405x350 X 400x400 400
CAE510513 mm 825x405 559x465 405x350 X 500x500 500
Omega10‐14 mm 1060x630 X 405x350 500x500 500
Omega16‐20 mm 1060x630 X 405x350 600x700 630
Omega28 mm 1650x824 X 920x400 600x1000 800
Crosssectionforamaximumlengthof20meters,airspeed:5to6meters/second
Averageloadlossesbyairflowdirectionchange,90°elboworbyT=1mmEC
Planawaterdrainagepointatthelowpointforpossibleprojectionofwaterintheducts.
Toensure the correct operation of the system, the duct network mustbe sized accordingto the air
flow delivered by the appliance (see table below). For very long or complicated networks please
contactus.
Theblowergratesmustbefittedwithregistersforbetterairdistribution.
Plan sufficientleeway to allow forthe removal of the filters on both sides of the extraction frames
(2of525x615mmonOmega10‐14‐16‐20and6of400x500mmontheOmega28).
Omegausinginversedblower(verticalfromthebottom):requiresablower boxtobebuiltunderthe
system(eitherusingmasonryifusingin‐groundductsorusinggalvanizedmetalifthereisventilation
space available underneath). This box should have a deflector to orient the flow to the different
networkblowerpoints.
Intakebox:to be madetomeasuredependingon the intakenetworkconfiguration.Itsdesign must
meetsoundinsulationcriteria(consideraddingoneormoresoundtrapsdependingontheappli ance
airflow).