Zodiac CAE Ducted handleiding
Handleiding
Je bekijkt pagina 4 van 26

H03846‐00.A1.EN–2012/10 3
Oméga(x1) Hygro
Control
(x1)
anti‐
vibration
studs(x6)
belt(x1for
Oméga10‐
14‐16‐20)
(x2for
Oméga28)
halfunionØ32
connectorto
glue+PVC
fitting1”+
joint(x1)
Withcondenser
option:half
unionØ50
connectorto
glue+joints(x2)
Withhotwater
batteryoption:
Ø20/22bushto
solder+joints
(x2)
1.3Operatingconditions
operatingrange:10°Cto40°C(temperatureintheswimmingpoolhall)
optimumoperatingconditions:between 25°Cand 30°C
HygroControlonrequest
1.4Technicalspecifications
Appliance
Dehumidifying
capacity*
Power
consumed*
Powerrestoredonthe
ambientair*
Available
pressure**
Airflow‐rate
Withoutoption L/h W W mmCE m³/h
CAE508 8 2710 6500 15 2040
CAE510 10 4040 9695 19 2720
CAE513 13.5 5430 13030 23 3400
Omega10 10 3840 9210 20 3000
Omega14 14 4390 10530 20 4000
Omega16 16 5830 13990 20 5000
Omega20 20 6430 15430 20 6000
Omega28 28 9900 23760 20 8500
*withambientairat+30°Candrelativehumidityof70%
**pressureavailablewithouthotwaterbattery,refertothebatteryloadlosses(see§2.7.1)
refrigerantgas:R407C
refrigerantcharge:seeproductinformationplate
2.Installation
2.1Installationrequirements
Installtheapplianceonalevelbase,toavoidanyoverflowsfromthecondensationtray,
Easyaccesstotheapplianceformaintenanceandconnections,
Warningaboutthefilter:leave1meteroffreespacearoundtheappliance,
Placenothinginfrontoforontheblowingandsuctiongrates,
anti‐vibrationstuds(supplied)mustbeinstalledundertheappliance,
For a swimming pool building with a high ceiling or visible roof frame: destratification of the upper
layers of the room = one or several fans with PVC blades or an air extractor with fresh air intake.
Warning!230VACappliances=mustbeoutsidevolume1(seeunder),
Riskofstratificatio n:
- heightoftheroom<4to5meters:mechanicalventilatorunitorextractor,
- heightoftheroom>5to8meters:ceilingfanswith largeblades.
Buildingrequirements:swimmingpoolbuilding=verydamproom,
Duringbuildingmakesurethat:
- thematerialsusedarecompatiblewithaswimmingpoolenvironment,
- the walls are sufficiently waterproofed and insulated to avoid condensation forming in the room
whenrelativehumidityreaches60to70%,
Lightstructurebuildings(verandas,shelters...):thereisnoriskofdeteriorationofthestructure,evenin
caseofdewastheyaredesignedtosupportthis(evenwitharelativehumidityof70%),