Precautions for installation of exhaust pipe:
1. The exhaust pipe must be installed when the water
heater is used.
2. The elbow and the straight pipe are combined into
a smoke exhaust pipe. One elbow is equivalent to 6
ft. But the total length of elbows and straight pipe
must not exceed 25 ft (7.5m).
WARNING
It is absolutely forbidden to use this water
heater without installing a smoke exhaust
pipe.
Installation
3.10 Venting Installation
6. The gap between the flue and the round hole in the
wall through which it passes cannot be
permanently filled with cement to facilitate
maintenance.
7. The exhaust vents shall not be installed in the
ventilation of the building and on the common flue.
4. When the flue passes through a wall made of
combustible materials, it must be covered with an
insulating flame retardant material greater than 1
inch thick.
5. The flue should not be hidden in the ceiling as much
as possible. If it is unavoidable, it needs to be
wrapped with flame-retardant insulation material,
covering a thickness of 1 inch or more. The distance
from the flue to the combustible item should be
greater than 1 ft.
3. The installation of gas water heater pipe should be
outward and downward the slope of 3° is such that
when the outdoor temperature is too low, the
condensed water does not flow back into the
interior of the water heater.
Elbow
Straight pipe
21