System Performance
The room with the highest water temperature requirement sets the design
water temperature for the whole system based on the calculations from
the previous section.
Usingthegraphaboveitispossibletolimitthespecicheatoutputtothe
required value.
The example above shows a design room air temperature of 20°C and
designheatoutputof52.5W/m².Basedona0.150m²K/W(1.5tog)oor
nishtheoorsensorshouldbesetto33°C(20°Croomair+13°CΔT)to
resultinginoorsurfacetemperatureof25°C(20°Croomair+5°CΔT).
Floor sensor setting for target heat output
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
0 10 20 30 40 50 60 70 8
0 90 100 110 120 130 140 150 160 170
Temperature dierence between design room air and
oor surface OR oor sensor °C
Floor sensor temperature
Floor surface temperature
Specic Heat Output, W/m²