System Performance
k
H
Value - W/m²K
Resistance of
Floor Covering,
tog
0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00
150mm Pipe
Centres
*
6.96 5.74 4.90 4.27 3.79 3.41 3.09 2.84 2.62 2.43 2.27 2.13 2.00
Using the system k
H
value to calculate the system heat output:
q = k
H
x ( T
water
– T
air
)
Example:
Theheatoutputthroughan18mmthick,≈1.25togtimberoor,over
Ultra-12,ttedwithpipeat150mmcentres,ina21°Croomheatedwith
40°Cwateris;
q = 3.41 x ( 40 – 21 ) = 3.41 x 19 = 64.79 W/m²
*
150 mm pipe centres with no overboarding or levelling compound. If you
areusingaoatingoordeckoverUltra-12beneaththeoornish,you
must also include its thermal resistance, for example:
18 mm Chipboard, R = 1.25 tog
18mmHiDECK18,R=0.45tog
Alternatively, using the system k
H
value to calculate the required water
temperature, knowing the required heat output:
T
water
= ( q / k
H
) + T
air
Example:
The water temperature required to produce a heat output of 55 W/m²,
througha3mmthickLVToornishonHiDECK18(0.30+0.45=0.75tog),
overUltra-12panels,ttedwithpipeat150mmcentres,ina22°Croomis;
T
water
= ( 55 / 4.27 ) + 22 = 13 + 22 = 35°C
q = SpecicHeatOutput,W/m² k
H
= SystemPerformanceFactor,W/m²K
T
water
= Mean water Temperature T
air
= Room Air Temperature