• Ensure that the sensor is tested
before the screed layer has
been laid. Warmup thermostats
typically use a 10 kΩ sensor.
Please to refer to the thermostat
manual for further details.
• The expected resistance
depending on temperature is
listed below.
Sensor resistance test
Sensor resistance by temperature - NTC10K
Temperature Resistance Temperature Resistance
0 °C 32.5 kΩ 16 °C 15.0 kΩ
2 °C 29.4 kΩ 18 °C 13.7 kΩ
4 °C 26.6 kΩ 20 °C 12.5 kΩ
6 °C 24.1 kΩ 22 °C 11.4 kΩ
8 °C 21.9 kΩ 24 °C 10.5 kΩ
10 °C 19.9 kΩ 26 °C 9.6 kΩ
12 °C 18.1 kΩ 28 °C 8.8 kΩ
14 °C 16.5 kΩ 30 °C 8.1 kΩ