Please also read the full instructions that follow this section.
Installation summary
• The suboor must be clean, level,
smooth, dry, frost-free, solid,
suitably weight-bearing and
dimensionally stable.
• Lay a damp proof membrane
over the suboor to prevent
water ingress.
• Install perimeter strip around the
perimeter of the room to allow for
dierential movement between
nished oor level and walls.
• Lay insulation board over the
membrane. Insulation should be
chosen and installed in line with
building regulations.
• Lay a vapour control layer over
the insulation to prevent water
ingress.
• Lay the Metro rail across the oor,
perpendicular to the intended
pipe runs�
• The rst rail must be placed
300mm from the wall and the 2nd
300mm from the 1st. Then, space
the rails at 1m centres ensuring
the pipe slots are aligned.
• Install the pipe in line with the projects working drawings. It is
recommended the pipe is installed using a double meander pattern as
this provides a more even surface temperature and higher heat output
than a single meander pattern.
• Install the pipe at the necessary spacing, alternating the rst run between
3 times and 1 times the design pipe spacing, before working back to the
manifold location securing into the Metro rail�
1 2
3 4
5
SR2
2 m < 5 mm