8 - Setting-up the encoder 
© Wachendorff Automation GmbH & Co. KG 
43 
8.2.4  End LSS configuration mode  
When the configuration is completed the changed parameters must be stored and the 
encoder has to be switched into PRE-OPERATIONAL state by using the following 
message sequence and a final reset (e.g. a power reset):   
Step 1 - store parameters:  
7E5h 
17h 
00h 
00h 
00h 
00h 
00h 
00h 
00h 
Table 8.6: End LSS configuration mode – Step 1 - store parameters  
Step 2 - Leave configuration mode 
7E5h 
04h 
00h 
00h 
00h 
00h 
00h 
00h 
00h 
Table 8.7: End LSS configuration mode – Step 2 - Leave configuration mode  
Step 3 - Reset (e.g. NMT "reset node" or power reset). 
8.2.5  Baudrate setting  
To set the baudrate send the following command: 
7E5h 
13h 
00h 
Baudrate 
00h 
00h 
00h 
00h 
00h 
CAN-ID   
Command 
Sub-Index 
Baudrate 
Byte2 
Byte3 
Byte4 
Byte5 
Byte6 
Table 8.8: set Baudrate 
The following baud rates can be selected: 
Value 
Baudrate 
0 
1 Mbit/s 
1 
800 kBit/s 
2 
500 kBit/s 
3 
250 kBit/s 
4 
125 kBit/s 
5 
100 kBit/s 
6 
50 kBit/s 
7 
20 kBit/s 
8 
10 kBit/s 
9 
Auto 
Table 8.9: Baudrate-Coding 