Wachendorff MA964802 handleiding

54 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 26 van 54
26 MA964802 - User manual
Modbus
Address
Description
Read
Write
Reset value
0 Device type RO EEPROM
1 Software version RO EEPROM
5 Address slave R/W EEPROM
500
Reload default data
The following values (commands) are accepted:
9999
Reload all the fault parameters
9998
Reload all default parameters, leaving the
baud rate, COM2 serial communication format
and the device address (slave address) unchanged
9997
Reload all default parameters, leaving
the baud rate and COM2 serial port format
unchanged
9996
Reload all default parameters, leaving the
device address (slave address) unchanged
Once the command received has been executed, the
device restarts so that it is correctly initialised
.
R/W 0
900
Alarm relay status (0 = O, 1 = On):
Bit 0 = Relay
Q1
Bit 1 = Relay
Q2
RO 0
901
Digital inputs status (0 = O, 1 = On):
Bit 0 =
DI.1
Bit 1 =
DI.2
Bit 2 =
DI.3
RO -
902
Key status (0 = released, 1 = pressed):
Bit 0 =
Bit 1 =
Bit 2 =
Bit 3 =
RO 0
903
Error ags
Bit 0 = Incorrect calibration data
Bit 1 = Incorrect parameters
Bit 2 = Incorrect status data
Bit 3 = EEProm memory writing error
Bit 4 = EEProm memory reading error
RO 0