44
BUILDING AUTOMATION
Object value for fan speed
• Parameter “Object value for Fan speed 1/2/3”
To define the object value to switch to each fan speed, that is, the value of the communication object “Fan speed--1byte”. Options:
Options: 1..255
The object value “0” defaults to fan speed off.
Parameter“ Forced operation function”
To enable forced operation. Options:
Disable
Enable
Select “Enable”, the 1-bit communication object “Forced Operation” is visible, and the following two parameters are also visible. It is used to set the activation
value of the forced operation and the action that can be performed under the forced operation.
• Parameter “Forced operation on object value ”
To set the telegram value to activate the forced operation. Options:
0=Force/1=Cancel
1=Force/0=Cancel
0=Force/1=Cancel: When the object “Forced Operation” receives the message value “0”, the forced operation is activated. When “1” is received, the forced
operation is cancelled.
1=Force/0=Cancel: When the object “Forced Operation” receives the message value “1”, it activates the forced operation. When it receives “0”, it cancels the
forced operation.
Note: During forced operation, the minimum operating time of fan speed for automatic operation still needs to be considered, except for the starting
fan speed, as it has its own minimum running time.
Forced operation is not activated by default after bus reset or after programming.
• Parameter “Limitation on forced operation ”
To define the limitation fan speed under forced operation. Options:
Unchange
1
1, off
2
2, 1
2, 1, off
3
3, 2
3, 2, 1
Off
Unchange: The fan speed of the fan remains unchanged and maintains the current operating state;
1: Only fan speed 1 is operated;
1, off: Only fan speed 1 and shut down the fan can be operated;
2: Only fan speed 2 can be operated;
2, 1: Only fan speeds 1 and 2 can be operated;
2, 1, off: Only fan speed 1, 2 and shut down the fan can be operated;
3: Only fan speed 3 can be operated;
3, 2: Only fan speed 3, 2 can be operated;
3, 2, 1: Only fan speed 1, 2 and 3 can be operated;
Off: Only shut down the fan can be operated;
Note: In the case of forced operation activation, if the current fan speed is not within the allowable range, the fan speed will switch to the nearest
allowable current fan speed. For example, the current fan speed is 1, and the allowed fan speed is 2 3, then when the forced operation is activated,
the fan speed will automatically switch to 2, if the fan speed is adjusted to 1 by manual mode, the running fan speed will also be 2.
In another case, if the current fan speed is 0, the allowed fan speed is 1, 2, 3, and the starting fan speed is 3. When the forced operation is activated,
the fan starts at fan speed 3 and then automatically switches to fan speed 1; if the current fan speed is 2, the allowed fan speed is 1, 2, when a forced
operation is activated, a fan speed 0 message is received, then the fan speed will switch to 1.In this case, the fan speed switches to the fan speed
near the target fan speed.