BUILDING AUTOMATION
Parameter “Monitoring control value”
To set whether to enable monitoring of external control values. Options:
No
Yes
When “Yes” is selected, the following parameters are visible.
• Parameter “Monitoring period of control value [10..65535]s
To set the monitoring period of external control value. If the control value is not received within this time, the device will consider the external controller
error and the fan coil will output according to the control value set by the next parameter. Options:
10...65535s
• Parameter “Reply mode of Obj. “Control value fault””
To define the feedback method when the external control value is incorrect. Options:
Respond after read only
Respond after change
Respond after read only: The object “Control value fault” sends the current state to the bus only when the device receives the read status from other bus
device or bus.
Respond after change: When the fault status changes or the device receives a request to read the status, the object “Control value fault” immediately
sends a message to the bus to report the current status.
• Parameter “Control value after fault occurs [0..100]%”
When an error occurs in the external controller, the fan coil will output the fan speed according to the control value set by this parameter. Options:
0...100 %
4.7.1.2 Parameter window “Fx: Status”
The parameter window “Fx: Status” setting interface is shown in Figure 4.22. This interface is used to set the status information of the fan operation.
Fig. 4.22 Parameter window “Fx: Status”
Parameter “Reply mode of Obj. “Status Fan ON/OFF” (1bit)”
To define reply mode for the fan’s operating status. Options:
Respond after read only
Respond after change
Respond after read only: The object “Status Fan ON/OFF” sends the current state to the bus only when the device receives the read status from other
bus device or bus.
Respond after change: When the fan coil operation status changes or the device receives a request to read the status, the object “Status Fan ON/OFF”
immediately sends a message to the bus to report the current status.
Parameter “Reply mode of Obj. “status Automatic”(1bit)”
This parameter is visible when the automatic operation is enabled, and defines the reply mode of the automatic operation status.
The object “Status Automatic” sends a message “1” to indicate that the automatic operation is activated, and “0” to indicate that the automatic operation
is exited. Options:
Respond after read only
Respond after change
Respond after read only: The object “Status Automatic” sends the current state to the bus only when the device receives the read status from other bus
device or bus.
Respond after change: When the automatic operation status changes or the device receives a request to read the status, the object “Status Automatic”
immediately sends a message to the bus to report the current status.
Parameter setting description in the ETS