Vimar 01532 handleiding

74 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 22 van 74
22
BUILDING AUTOMATION
Fig. 4.13 Parameter window “Output X: Heating actuator (without controller)_1byte (Continuous)”
Parameter “Valve type”
This parameter setting the valve type of the heating valve control. Options:
Normal (de-energised closed)
Inverted (de-energised open)
As for valve, “Normal(de-energised closed)” is applied for normal closed valve, “Inverted(de-energised open)” is applied for normal open valve.
Parameter “If bus failure, contact is”
This parameter setting the contact position when bus failure. Options:
Unchange
Open
Close
When select “Unchange”, contact of the channel will not change when bus failure;
When select “Open”, contact of the channel will open when bus failure;
When select “Close”, contact of the channel will close when bus failure;
After bus failure only when the relay possess enough energy can it perform the above setting.
Parameter “If bus recovery, valve position”
This parameter setting the valve position when bus recovery. Options:
0%[Closed]
10%[26]
20%[51]
...
80%[204]
90%[203]
100%[Open])
For example, 20%, the PWM cycle time as 100s(1min40s),then the cycle time of valve switching behavior is on for 20s, off for 80s.
Parameter setting description in the ETS

Bekijk gratis de handleiding van Vimar 01532, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkVimar
Model01532
CategorieNiet gecategoriseerd
TaalNederlands
Grootte15582 MB